Addressable Relay Module IDP-RELAY

The IDP-RELAY is an addressable relay module for use with the Honeywell Farenhyt Series fire alarm control panels (FACPs). The IDP-RELAY allows a Farehyt FACP to switch discrete contacts by code command. The relay contains two isolated sets of Form C contacts, which operate as a DPDT switch. No supervision is provided for the notification appliance circuit. The IDP-RELAY contacts can be used for virtually any normally open or normally closed application. Each IDP-RELAY is programmed with a unique signaling line circuit (SLC) loop address. When an event occurs that controls the IDP-RELAY, the relay is triggered by the FACP.
  • Two sets of Form contacts
  • Contacts are rated for a variety of amps (see Specifications)
  • Panel controlled status LED that flashes green in normal state and is solid red in alarm
  • Relay programming is completely flexible can be mapped to zone conditions
  • Polling LED visible through the cover plate
  • Rotary address switches for fast installation
  • SEMS screws for easy wiring: UL Listed, CSFM Listed
  • MEA Listed 386-02-E Vol. II
  • SPECIFICATIONS*
    Physical: 4.275″ H x 4″.675 W x 1.4 D
    Shipping Weight: 6.3oz (196g)
  • ELECTRICAL RATINGS
    Operating Voltage: 15 to 32VDC
    Standby Current: 300μA max @ 24VDC (one
    communication every 5 sec. with LED enabled)
    LED Current: 5.5 mA (with LED latched on)
    Relay Contact Ratings:
    2.0A @ 25VAC (PF=.35), non-coded
    3.0A @ 30VDC resistive, non-coded
    2.0A @ 30VDC resistive, coded
    0.46A @ 30VDC (L/R=20ms), non-coded
    0.7A @ 70.7VAC (PF=.35), non-coded
    0.9A @ 125VDC resistive, non-coded
    0.5A @ 125VAC (PF=.75), non-coded
    0.3A @ 125VAC (PF=.35), non-coded
  • ENVIRONMENTAL
    Operating Temperature: 32º-120ºF (0ºC – 49ºC)
    Humidity: 10 to 93% non-condensing)
    For more information
    Learn more about Honeywell’s Farenhyt Series and
    other products available by visiting
    www.farenhyt.com
    Honeywell Security & Fire
    12 Clintonville Road
    Northford, CT 06472
    800-328-0103
  • ORDERING INFORMATION
    IDP-RELAY: Relay Module
  • ACCESSORIES
    SMB500: 4” Square Surface Mount Electrical Box
    CB500: Module Barrier. Used to separate power
    limited and non-power limited wiring in a junction
    box.