The Siemens – Fire Safety XTRI-series Intelligent Interface Modules are available in
three (3) individual types:
Advanced troubleshooting is provided by compatible
panels by identifying when a XTRI-series interface
module is configured as an isolator, but is wired
incorrectly in a polarity-insensitive mode.
Each Model XTRI-series device has a multi-color LED that
flashes when GREEN operating in Normal mode; AMBER
if the unit is in a `Trouble’ condition, and RED to
indicate a change of status.
Model XTRI-S
This single-input interface module can only monitor and
report the status of a N.O. or N.C. contact.
Model XTRI-R
Through the use of an addressable ‘Form C’ relay, the Model
XTRI-R relay and contact device input are controlled at the
same address. The relay and input contact can be controlled
as a separate function from a Siemens compatible FACP. The
relay is typically used where control or shunting of external
equipment is required.
Model XTRI-D
Model XTRI-D is a dual-input module that is designed to
supervise and monitor two (2) sets of dry contacts. Model
XTRI-D only requires one (1) address, but responds
independently to each input. Model XTRI-D is ideal for
monitoring a water-flow switch and its respective valve
tamper switch.
OPERATING VOLTAGE RANGE: | 13VDC – 32VDC | |||||||
RELATIVE HUMIDITY: | 0 – 95% (non-condensing) |
|||||||
`ACTIVE’ OR `STANDBY’ CURRENT, MAX.: | 500μA | |||||||
LINE SIZES AMERICAN WIRE GAUGE (AWG) | 14 AWG, max. 18 AWG, min. |
|||||||
CURRENT DRAW MAX | AVG. | XTRI-S | 650μA | ||||||
XTRI-R | 750μA | |||||||
XTRI-D | 950μA | |||||||
RELAY RATINGS: (for Model XTRI-R) |
||||||||
RESISTIVE: | 4 Amps | 125 VAC | |||||||
4 Amps | 30 VDC | ||||||||
INDUCTIVE: | 3.5A, 120 VAC (0.6 pF) | |||||||
3.0A, 30 VDC (0.6 pF) | ||||||||
2.0A, 120 VAC (0.4 pF) | ||||||||
2.0A, 120 VAC (0.35 pF) | ||||||||
2.0A, 30 VDC (0.35 pF) |