- Warranty 10 year
- Applications
-
- Bedrooms
- Hospitals
- Hotels
- Medium to large buildings
- Offices
- University campuses
- Clean rooms
- Warehouses
- B&Bs/guest houses
- Cafes
- Care homes
- HMOs
- Restaurants
- Small to medium buildings
- Fire Type Fast and slow burning fires
- Wireless No
|
- Heat classification A1R
- Analogue value nominal 23
- Analogue value (- tolerance) 0
- Analogue value (+ tolerance) 4
- Analogue value 23 +4/-0
- Alarm level analogue value 55
- Chamber type Chevron
|
- Colour White
- Sensor configuration Horizontal optical bench housing infra-red emitter and sensor, arranged radially to detect forward scattered light.
- Weight 105g
- Materials housing Polycarbonate
- Materials terminals Nickel plated stainless steel
- Product diameter 100mm
- Detection principle
- Photo-electric light scattering.
- Temperature sensitive resistance.
- Product diameter 3.94in
- Product height (wo/base) 50mm
|
- Standards
-
- Approvals
-
- FG
- SBSC
- BOSEC
- LPCB
- VdS
- CPR
|
- Protocol voltage 5 to 9V peak to peak
- Protocol voltage (max) 9V
- Protocol voltage (min) 5V
- Power-up surge current 1mA
- Maximum power-up time 10 seconds
- Status indicator – Alarm Red
- Quiescent current 470μA
- Quiescent current tested at 24V dc
- Supply voltage (max) 28V dc
- Supply voltage (min) 17V dc
- Supply voltage (Vmin-Vmax) 17 to 28V dc
- Terminal functions L2 +L2 Loop in & out positive
- Terminal functions L1 in +L1 in
- Terminal functions L1 out +L1 out
- Polarity L1 & L2 are polarity insensitive
|
- Humidity (max) 0% RH
- Humidity (min) 95% RH
- Humidity Note no condensation or icing
- Humidity 95% to 0% (no condensation or icing)
- Operating temperature -40 to 70°C
- Operating temperature (max) 70°C
- Operating temperature (min) -40°C
- IP rating Value IP44
- Operating temperature (min) -40°F
- Operating temperature (max) 158°F
- Operating temperature -40 to 158°F
|