Integrated in the detector housing is a fan which, in conjunction with the sampling pipes, ensures an uninterrupted supply of air to
the detector housing. Airflow monitoring detects any pipe blockages and pipe breakages in the sampling pipe.
The ASD 532 can be equipped with the following smoke sensor type:
• SSD 532-1 Sensitivity range 0.5 %/m to 10%/m
• SSD 532-2 Sensitivity range 0.1%/m to 10%/m
• SSD 532-3 Sensitivity range 0.02%/m to 10%/m
The ASD 532 aspirating smoke detector has two slots for additional modules. The following modules can be fitted:
• XLM 35 extended Line Module
• RIM 36 Relay Interface Module with 5 relays (max. units);
• SIM 35 Serial Interface Module
The ASD 532 can be connected to a superordinate FACP by
means of potential-free change-over contacts.
With the installation of an XLM 35, the ASD 532 can be ideally
connected via the addressable loop to the SecuriFire and Integral
fire alarm systems.
The RIM 36 is available as a further installation option. This module enables the availability of all three pre-signal levels as well as
the states “smoke sensor dirty” and “LS-Ü blockage” as relay contacts. The relays are also freely programmable via the “ASD Config” configuration software.
Up to 250 ASDs can be networked with the SIM 35; they can then
be visualized and operated from a PC using “ASD Config”.
The ASD 532 aspirating smoke detector can be used for:
Technical data | ||||||
Type | ASD 532 | |||||
Supply voltage | range | 14 to 30 (UL/FM = 16.4 bis 27) | VDC | |||
Max. power consumption, measured in | typical | |||||
Fan speed level III and at è | 14 VDC | 24 VDC | ||||
ASD 532 | Quiescent / fault | approx. 170 | approx. 100 | mA | ||
Alarm | approx. 200 | approx. 115 | mA | |||
additionally with 1x RIM 36 | approx. 30 | approx. 15 | mA | |||
additionally with 2x RIM 36 | approx. 60 | approx. 30 | mA | |||
additionally with XLM 35 | approx. 15 | approx. 5 | mA | |||
additionally with SIM 35 | approx. 15 | approx. 5 | mA | |||
SMM 535 (not from ASD but rather from PC via USB connection) | max. 100 | mA | ||||
Switch-on current peak (caused by EMC protection elements on the ASD supply input) | approx. 5 | A | ||||
for max. 1 | ms | |||||
Sampling pipe length | see T 140 421, Sec. 4.2.1 | |||||
Sampling pipe diameter, typical (inner/outer) | Ø 20 / 25 | mm | ||||
Max. number of sampling holes | see T 140 421, Sec. 4.2.1 | |||||
Sampling hole diameter | Ø 2 / 2.5 / 3 / 3.5 / 4 / 4.5 / 5 / 5.5 / 6 / 6.5 / 7 | mm | ||||
Response range | EN 54-20, Class A, B, C | |||||
Protection type compliant with IEC 529 / EN 60529 | 54 | IP | ||||
Ambient conditions compliant with IEC 721-3-3 / EN 60721-3-3 | 3K5 / 3Z1 | class | ||||
Extended ambient conditions: | ||||||
· Detector housing temperature range | –20 – +60 (UL max. +40) | °C | ||||
· Sampling pipe temperature range | –20 – +60 | °C | ||||
· Max. permissible temperature fluctuation in detector housing and sampling pipe operation | 20 | °C | ||||
· Max. permissible storage temperature for detector housing (without condensation) | –30 – +70 | °C | ||||
· Ambient pressure difference between detector housing and sampling pipe (sampling holes) | must be identical | |||||
· Humidity ambient condition for detector housing (transient without condensation) | 95 | % rel. h | ||||
· Humidity ambient condition (continuous) | 70 | % rel. h | ||||
Max. loading capacity, relay contact | 50 (UL max. 30) | VDC | ||||
1 | A | |||||
30 | W | |||||
Max. loading capacity per OC output (dielectric strength 30 VDC) | 50 | mA | ||||
Plug-in terminals | 2.5 | mm² | ||||
Cable entry for cable Ø | Ø 5 – 12 (M20) / Ø 9 – 18 (M25) | mm | ||||
Noise level | min. (if fan speed level I) | 24.5 | dB (A) | |||
max. (at fan speed level III) | 39.5 | dB (A) | ||||
Housing material | ABS blend, UL 94-V0 | |||||
Colour | grey 280 70 05 / anthracite violet 300 20 05 | RAL | ||||
Approvals | EN 54-20 / EN 54-27 / FM 3230-3250 / UL 268 / UL 268A / ULC-S529 | |||||
Dimensions | ASD 532 (W x H x D) | 195 x 333 x 140 | mm | |||
Weight | ASD 532 (incl. SSD 532-x) | 2,000 | g |