Edwards EST SIGA-CC1 Single Input Signal Module

SIGA-CC1/MCC1 Single Input Signal Modules and SIGA-CC2/ MCC2 Dual Input Signal Modules are part of EDWARDS's Signature Series system. They are intelligent analog addressable devices used for connecting, upon command from the loop controller, supervised Class B signal or telephone circuits to their respective power inputs. The power inputs may be polarized 24 Vdc to operate audible and visible signal appliances or 25 and 70 VRMS to operate audio evacuation speakers and firefighter’s telephones. The actual operation of the SIGA-CC1/MCC1 and SIGA-CC2/ MCC2 is determined by the “personality code” selected by the installer. It is downloaded to the module from the Signature loop controller during system configuration.

Operating voltage range 15.20 to 19.95 VDC
Current
Standby 310 µA
Activated 135 µA
Maximum line impedance Refer to the control panel installation manual
Ground fault impedance 10 kΩ
EOLR 47 kΩ (P/N EOL-47)
Circuit designation
Signaling line circuits Class A, Style 6 or Class B, Style 4
Telephone riser circuits Class B, Style 4
Notification line circuits Class B, Style Y
Wire sizes 12 to 18 AWG (1.0 to 4.0 mm²)
Storage temperature range −4 to 140°F (−20 to 60°C)

Operating voltage range 15.20 to 19.95 VDC
Current
Standby 310 µA
Activated 135 µA
Maximum line impedance Refer to the control panel installation manual
Ground fault impedance 10 kΩ
EOLR 47 kΩ (P/N EOL-47)
Circuit designation
Signaling line circuits Class A, Style 6 or Class B, Style 4
Telephone riser circuits Class B, Style 4
Notification line circuits Class B, Style Y
Wire sizes 12 to 18 AWG (1.0 to 4.0 mm²)
Storage temperature range −4 to 140°F (−20 to 60°C)