EDWARDS iO64 Intelligent Life Safety System

The Edwards EST iO64 intelligent life safety system offers the power of high-end intelligent processing in a configuration that delivers an uncomplicated solution for small to mid-sized applications. With intelligent detection, electronic addressing, automatic device mapping, optional Ethernet® connectivity, and a full line of easily-configured option cards and modules, this flexible system offers advanced features that benefit building owners and contractors alike.
The iO64 provides one Class B analog device loop that supports up to 64 device addresses, and two Class B Notification Appliance Circuits (NACs). Optional Class A device wiring is available with the use of a module.

  • System Capacity:
    • Loops: 1 Class A or Class B intelligent device loop
    • Device Addresses: Supports up to 64 intelligent device addresses (any combination of detectors and modules)
    • Notification Appliance Circuits (NACs): 2 Class B NACs (optional Class A with SA-CLA module)
  • Operating Voltage:
    • Input Voltage: 115 VAC or 230 VAC (model-dependent, typically 120 VAC @ 60 Hz standard in North America)
    • Loop Voltage: 19 VDC nominal, 15.2–19.95 VDC range
    • Maximum Loop Voltage: 20V peak-to-peak
  • Current Consumption:
    • Standby Current: 125 mA typical (base system, excluding devices)
    • Alarm Current: Up to 3.5 A max (dependent on NAC load and auxiliary power usage)
    • Loop Current: 250 µA (standby), 400 µA (activated) per device typical
  • Power Supply:
    • Output: 24 VDC, 3.5 A total (shared between NACs and auxiliary power)
    • Battery Backup: Supports sealed lead-acid batteries, typically 7–18 Ah (depending on enclosure and standby requirements)
    • Battery Charger: Built-in, supervised, 27.6 VDC charging voltage
  • Notification Appliance Circuits (NACs):
    • Output: 24 VDC, 1.5 A max per NAC (3.5 A total system limit)
    • Synchronization: Supports Genesis horn silence and UL 1971-compliant strobe synchronization
    • Wiring: Class B standard; Class A with optional SA-CLA module
  • Loop Specifications:
    • Wiring: Class B (Style 4) or Class A (Style 6/7 with SA-CLA module)
    • Maximum Loop Length: Up to 10,000 ft (3,048 m) with #18 AWG (0.75 mm²) twisted-pair, unshielded
    • Compatibility: Edwards Signature Series intelligent detectors and modules
  • Environmental Specifications:
    • Operating Temperature: 32°F to 120°F (0°C to 49°C)
    • Storage Temperature: -4°F to 140°F (-20°C to 60°C)
    • Humidity: 0 to 93% RH, non-condensing
  • Display and Interface:
    • Display: 4 x 20 character backlit LCD
    • Indicators: LEDs for Power (green), Alarm (red), Trouble (yellow), Supervisory (yellow), and Silence (yellow)
    • Controls: Two programmable switches with LEDs and custom slide-in labels
  • Wiring:
    • Terminals: Screw terminals accepting #18 AWG (0.75 mm²) to #12 AWG (2.5 mm²)
    • Connections: Standard unshielded wiring; supports retrofit applications
  • Communication and Connectivity:
    • Addressing: Electronic addressing with automatic device mapping
    • Optional Modules:
      • SA-DACT: Dual-line dialer/modem (supports Contact ID, 4/2 formats)
      • SA-ETH: Ethernet port for diagnostics, programming, and reporting
      • SA-232: RS-232 serial port for printers or computers
    • Annunciators: Supports up to 8 serial annunciators (LCD, LED, or graphic)
  • Physical Characteristics:
    • Dimensions: Approximately 14.5″ H x 12.5″ W x 4.25″ D (368 mm x 318 mm x 108 mm)
    • Weight: ~15 lbs (6.8 kg) with enclosure, without batteries
    • Enclosure: Surface-mount, red or gray door options (e.g., iO64RD = red door, iO64GD = gray door)
  • Certifications:
    • Listings: UL 864, ULC-S527, CSFM, FM Approved
    • Compliance: NFPA 72, ADA accessibility standards
  • Additional Features:
    • Diagnostics: Built-in reporting for maintenance alerts, alarm verification by point, and detector sensitivity
    • Programming: Via front panel or optional laptop configuration utility
    • Retrofit Compatibility: Uses existing wiring in most cases, no shielded cable required
    • Relay Outputs: Form C contacts for Alarm and Trouble, Form A for Supervisory