GL61-Addressable Manual Call Points

The GL61-MS is a Addressable Manual Call Point is used for sending a manual alert to an addressable control panel in case of emergency. It has two indicator lights. When in the monitor state, green LED flashes every 3 seconds. Red indicates that the trigger is pressed.

This manual call point is used together with the Addressable Fire Alarm Control Panel produced by our company. It employs the electro-encoding method. The encoding method can refer to the instruction of address encoder.

Features: 

  • EN 54-11:2001 + A1:2005 Compliance
  • Using microprocessor technology
  • Digital addressing
  • Non-breakable glass and hammerless
  • Safe to operate and easy to reset
  • Semi-flash Mounted, indoor application
   
CATEGORY PARAMETER
Operation Voltage DC 22V
Standby Indicator Red LED flash every 6 seconds
Alarm Indicator Red LED flash quickly
Standby Current@24VDC ≤400uA
Alarm Current @24VDC ≤2mA
Range of Address 1~220
Connection Two wires, non-polarity
Operation Temperature  -10℃~+50℃
Operation Humidity ≤495%RH (no condensation)
Dimension 86x86x42mm
Weight 85 g
Color Red
Material ABS
Warranty 1 year