Input module BX-I2

The BX-I2 contains one primary input for polling potential-free contacts and one opto-isolator input, which can be used for monitoring an external voltage if necessary. It meets the SecuiLine eXtended specification for operation on the addressable loop of the SecuriFire fire detection system. The BX-I2 can be connected to the SecuriLine eXtended addressable loop of the SecuriFire fire detection system. The BX-I2 contains one primary input for polling potential-free contacts. This can be inverted as well as parameterised with / without line monitoring, further is can be defined as logical element input or detector zone. The module has in addition an opto-isolator to monitor a potential-dependent signal or an external power supply. To install the module is used a plastic housing with IP 66 protection, which can be equipped with various cable inlets as required. Addressing and parameter assignment for the BX-I2 is performed with PC software via the fire alarm control panel. The module includes a short-circuit isolator. In the event of wire breakage or a short-circuit, this functionality ensures that the fault is localized and at the same time maintains the full operability of the addressable loop.
  • Power supply via the SecuriLine eXtended
  • Addressing and parameter assignment with PC software via
    SecuriLine eXtended
  • Up to 62 modules can be connected per loop
  • 1 monitored primary input
  • 1 opto-isolator input for voltage monitoring
  • Integrated short circuit isolator
  • Robust plastic housing

Function: Input module
Operating voltage: 12 to 30 VDC
Power consumption (module’s power consumption only): 0.46 mA
Signal transmission: Serial data transmission, 2-line technology
Protection type: 66 with map case IP
Ambient temperature: -20 to +60 -°C
Connection: Screw terminals max. 1.5 mm2
VdS approval: G212023
EU certificate of conformity: (EN 54-17/18) 0786-CPD-21143
Dimensions (H x W x D): 67 x 67 x 20 mm
Dimensions with map case (H x W x D): 94 x 94 x 81 mm
Monitored inputs: 1 Pc.
Connection: IN1- and IN1+ , potential-free contacts
Polling current: 10 mA
Polling voltage: 3-6 V
Termination resistance: 180 Ω
Alarm resistance: 180 Ω
Line resistance : max. 30 Ω
Polling impulse: 165 μs
Polling cycle: 100 ms
Input filter: 10 μs
Periodic duration: > 8
(switching states which last longer than 500 ms and whose repetition time is greater than 8 s are recorded)
Line length: max. 30 m
Connection: Screw terminals max. 1.5 mm2
Input voltage monitoring, potential-dependent: 1 Pc.
Connection: IN3- and IN3+, potential-dependent signals
Input voltage range: 0 to 30 V
Input current max.: 6 mA
Input resistance: 4,900 Ω
Galvanic separation: By opto-isolator
Line length: max. 1,000 m
Connection: Screw terminals max. 1.5 mm2
Input voltage monitoring, potential-free: 1 Pc.
Connection: IN3- and VEXT, potential-free signals
Input voltage range: 0 to 30 V
Input current: @10 V 0,4 mA, @24 V 1,9 mA
Input resistance: 10 kΩ
Galvanic separation: By opto-isolator
Line length: Max. 1,000 m
Connection: Screw terminals max. 1.5 mm