Isolator and Isolator Base 55000-720APO

Isolator The Isolator is placed at intervals on the loop and ensures that, in the case of a short circuit, only the section between the isolators will be affected. When the short circuit is removed, the isolators automatically restore power and data to the isolated section. The Isolator can only be used with an Isolator base and will not fit a standard addressable base. • Detects wiring short-circuits using patented technology • Minimizes disruption from short circuits • Automatic de-isolation on short-circuit removal • Up to 20 detectors (or equivalent) may be installed between isolators Isolator Base
  • The Isolator Base is only suitable for use with the Isolator.
EMC Directive 2014/30/EU
  • The Isolator and Isolator Base comply with the essential requirements of the EMC Directive 2014/30/EU, provided that they are used as described in this datasheet. A copy of the Declaration of Conformity is available from the Apollo website: www.apollo-fire.co.uk Conformity of the Isolator and the Isolator Base with the EMC Directive, does not confer compliance with the directive on any apparatus or systems connected to them. Construction Products Regulation 305/2011/EU The Isolator complies with the essential requirements of the
  • Construction Products Regulation 305/2011/EU. A copy of the Declaration of Performance is available from the Apollo website: www.apollo-fire.co.uk

Apollo Isolator (XP95 and Discovery) – 55000-720APO

The Isolator is placed at intervals on the loop and ensures that, in the case of a short circuit, only the section between the isolators will be affected. When the short circuit is removed, the isolators automatically restore power and data to the isolated section.

Key Features:

Detects wiring short-circuits

Minimises disruption from short-circuits

Automatic de-isolation on the short-circuit removal

Up to 20 detectors or their equivalent load, may be installed between isolators

  • Operating voltage: 17 V – 28 V dc (max dc voltage range)
    Digital communication: XP95, Discovery and
    CoreProtocol compatible
  • Modulation voltage: 5 – 9 V peak to peak
  • Quiescent current 35 µA
  • Surge current 0 mA
  • Maximum current drawn 8.5 mA
  • Maximum line impedance 50 Ω
  • Operating temperature- 30 ºC to +80 ºC
  • Humidity (no condensing or icing) 10% to 93% RH
  • Standards and approvals CPR, LPCB, VdS
  • Dimensions 100 mm diameter x 3.5 cm height
  • Materials White flame-retardant
    polycarbonate