Manual Call Point XMS-S / XMS-D

The XMS-Series of manual pull stations are a complete addressable and conventional pull station portfolio including single action, dual-action, 2-Stage, and metal versions. The addressable versions feature built-in Class X (Style 7) isolation capability for increased system survivability. All models feature a T-45 reset key to match the fire alarm panel enclosure. Addressable models also feature a tri-color status LED to indicate normal, alarm, and trouble status. All models utilize one address. The manual stations can be commissioned to operate in non-isolation (polarity insensitive) or isolation with Class X mode of operation.

Models XMS-S, XMS-D, XMS-DA, XMS-2S, and XMS-M are compatible with Siemens
FACPs. The Model XMS-S is a single action pull station in a plastic housing that
requires one action by the user to initiate the alarm. Models XMS-D, XMS-2S, and
XMS-DA are dual-action pull stations in a plastic housing that require two actions by
the user to initiate an alarm. The Model XMS-M is a single action pull station in a
metal housing that requires one action by the user to initiate the alarm. These
models are field installed addressable devices containing advanced control panel
communication technology.
The XMS-Series manual pull stations feature a “maintenance trouble” that places the
fire alarm panel into a trouble condition if an XMS is accidentally left in an armed
status when the cover is removed for maintenance work.
This technology provides bi-directional communication
with the connected control panel. To reset the stations,
insert the Siemens T-45 key provided into the key lock
and turn the key 10-15 degrees counterclockwise as the
arrow shows. The cover will move upward to the normal
position. Rotate the key clockwise and remove key from
the lock. At Normal position the top of the Cover is flush
with the top surface of the Base. Reset the Fire Alarm
Control Panel to clear the alarm.
The addressable XMS pull station variants are
compatible with all current models of Desigo Fire Safety
& Cerberus PRO commercial fire alarm control panels.
These devices can be wired in either Isolation Mode or
Polarity Insensitive Mode Wiring.
The XMS-S & XMS-M manual station front cover has a recess pocket to pull down and
locks in position after the alarm is initiated. The XMS-D, XMS-DA & XMS-2S manual
stations have an additional lever labeled “PUSH HERE THEN” to get access to the front
cover pocket to initiate the alarm.

Operating Voltage Range 13 – 32VDC
Max Average Operating Current @ 24v: 500µA
Operating Temperature Range 32° ─ 120°F
(0° ─ 49°C)
Operating Humidity Range 0 ─ 95%, RH