Notifier Manual Call Point NBG-12LX

  • Dual-Action Operation:
    • It requires two distinct actions (pushing in and pulling down) to activate, reducing the risk of accidental alarms.
  • Addressable:
    • This allows the fire alarm control panel to pinpoint the exact location of the activated pull station, improving response times.
  • Key-Lock Reset:
    • It features a key-lock reset, enabling authorized personnel to reset the station after activation.
  • Intelligent Communication:
    • It’s designed to work with Notifier’s intelligent fire alarm control panels, utilizing either Flash Scan® or CLIP communication protocols.
  • LED Indication:
    • A built-in bicolor LED provides visual status indication: flashing green for normal operation and steady red when activated.
  • ADA Compliance:
    • It meets ADA (Americans with Disabilities Act) requirements, ensuring accessibility.
  • Construction:
    • It’s designed for durability and includes features like Braille text on the handle.
  • Installation versatility:
    • It can be surface or semi flush mounted.
  • Applications:
    • Used in commercial and industrial fire alarm systems.

Electrical Specifications:

  • Normal Operating Voltage: 24 VDC   
  • Maximum SLC loop voltage: 28.0 VDC
  • Maximum SLC loop current: 375 µA
  • Maximum SLC alarm current: 5 mA

Environmental Specifications:

  • Temperature Range: 32°F to 120°F (0°C to 49°C)   
  • Relative Humidity: 10% to 93% noncondensing

Physical Specifications:

  • Shipping Weight: 9.6 oz. (272.15 g)   
  • Mounting:
    • Semi-flush mount to a standard single-gang, double-gang, or 4″ (10.16 cm) square electrical box.   
    • Surface mount to the model SB-10 or SB-I/O surface backbox.   

Key Features:

  • Dual-action operation (pushing in and pulling down).   
  • Addressable communication.
  • Key-lock reset.
  • Built-in bicolor LED (flashing green for normal, steady red for alarm).   
  • ADA compliance.
  • Rotary decimal switches for address setting.   

Important Notes:

  • The NBG-12LX is compatible with Notifier’s intelligent fire alarm control panels, utilizing FlashScan® or CLIP communication protocols.   
  • It is designed for indoor use in dry locations.   
  • It conforms to ANSI/UL Standard 38 and ULC Standard S528.
  • UL Listed:
    • It is listed under Underwriters Laboratories (UL) standards, specifically UL 38, which is the standard for manually actuated signaling boxes.
  • ULC Listed:
    • It is also listed under Underwriters Laboratories of Canada (ULC) standards, specifically ULC-S528, which is the standard for manually actuated signaling boxes for fire alarm systems.
  • ADA Compliant:
    • It meets the requirements of the Americans with Disabilities Act (ADA), ensuring accessibility for individuals with disabilities.   
  • CSFM Approved:
    • It is approved by the California State Fire Marshal.