SIGA-CR Control Relay Module

The SIGA-CR Control Relay Module provides a Form “C” dry relay contact to control external appliances such as door closers, fans, dampers etc. This device does not provide supervision of the state of the relay contact. Instead, the on-board microprocessor ensures that the relay is in the proper ON/OFF state. Upon command from the loop controller, the SIGA-CR relay activates the normally open or normally-closed contact.
Weight 0.2 lbs
Manufacturer UTC Fire & Security
Brand Edwards, EST
Condition New
Unit of Measurement EA (Each)
Production Status Active
Type Intelligent Module
Style Control, Input/Output, Relay
Programming Electronic
Protocol Signature Loop Controller
Voltage 19 VDC
Voltage Range 15.20 – 19.95 VDC
Series

 

Operating voltage 15.20 to 19.95 VDC
Current Standby Activated
85 µA
Ground fault impedance 10 kΩ
Contact ratings (pilot duty) 24 VDC at 2 A
120 VAC at 0.5 A
Relay type Form C, programmable Class E
Circuit designation Signaling line circuits
Class A, Style 6 or Class B, Style 4
Wire size 12 to 18 AWG (1.0 to 4.0 mm²)
LPCB/CPR electrical box
Requirements
Minimum size W × H × D
Plastic box with cover plate, no gaps
or unused holes
2.4 × 3.5 × 1.5 in. (60 × 85 × 38 mm)
Compatible electrical boxes 2-1/2 in. (64 mm) deep single-gang
box; Standard 4 in. square,1-1/2 in.
(38 mm) deep box
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93%, noncondensing
Storage temperature range −4 to 140°F (−20 to 60°C)
SLC Circuit Class A or Class B