Weight | 0.2 lbs |
---|---|
Manufacturer | UTC Fire & Security |
Brand | Edwards, EST |
Condition | New |
Unit of Measurement | EA (Each) |
Production Status | Active |
Type | Intelligent Module |
Style | Control, Input/Output, Relay |
Programming | Electronic |
Protocol | Signature Loop Controller |
Voltage | 19 VDC |
Voltage Range | 15.20 – 19.95 VDC |
Series | Signature Serie |
Operating voltage 15.20 to 19.95 VDC
Current Standby Activated
85 µA
Ground fault impedance 10 kΩ
Contact ratings (pilot duty) 24 VDC at 2 A
120 VAC at 0.5 A
Relay type Form C, programmable Class E
Circuit designation Signaling line circuits
Class A, Style 6 or Class B, Style 4
Wire size 12 to 18 AWG (1.0 to 4.0 mm²)
LPCB/CPR electrical box
Requirements
Minimum size W × H × D
Plastic box with cover plate, no gaps
or unused holes
2.4 × 3.5 × 1.5 in. (60 × 85 × 38 mm)
Compatible electrical boxes 2-1/2 in. (64 mm) deep single-gang
box; Standard 4 in. square,1-1/2 in.
(38 mm) deep box
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93%, noncondensing
Storage temperature range −4 to 140°F (−20 to 60°C)
SLC Circuit Class A or Class B