SIGA-OSHD Multi Sensor Detector

The Signature Optica Series SIGA-OSHD smoke detector brings advanced optical sensing technology to a practical design that increases efficiency, saves installation time, cuts costs, and extends life safety and property protection capabilities. Continuous self-diagnostics ensure reliability over the long-haul, while environmental compensation helps reduce maintenance costs.
The SIGA-OSHD provides an optical smoke sensor and a rate-of-rise heat sensor with a fixed temperature setting. Together these sensors efficiently detect smoldering fires, as well as fast flaming fires. Like all Signature Optica Series detectors, the SIGA-OSHD is an intelligent device that gathers analog information from multiple optical sensors, converting this data into digital signals. Utilizing dual optical wavelengths combined with multiple detection angles, the SIGA-OSHD differentiates particles that are not representative of actual smoke. Particle data is input into digital filters which feed a series of ratios removing signal patterns that are typical of nuisance sources, thus reducing unwanted alarms. To make an alarm decision, the detector’s on-board microprocessor measures and analyzes all optical sensor readings and compares this information to preprogrammed settings.
  • Operating voltage- 15.20 to 19.95 VDC
  • Normal operating current- 32 µA
  • Alarm current- 45 µA
  • Vibration level- 10 to 35 Hz, with an amplitude of 0.01 in.
  • Smoke Sensitivity Range- UL/ULC: 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) obscuration
  • Rate-of-rise rating- 15°F/min (8°C/min)
  • Fixed temperature rating- 135°F (57.2°C). Actual alarm point 129 to 141°F (53.9 to 60.6°C).
  • Air velocity- 0 to 4,000 ft./min (0 to 20.32 m/s)
  • Wall mounting- 12 in. (305 mm) max. from ceiling
  • Spacing, heat detectors- Max. 50 ft. (15.2 m) centers
  • Compatible bases- See Ordering Information
  • Compatible detector testers- Testifire 1000, Testifire 2000
  • Operating environment- 32 to 100°F (0 to 38°C), 0 to 93% RH, noncondensing
  • Construction- High Impact Engineering Polymer, White
  • Storage temperature- -4 to 140°F (-20 to 60°C)
  • Environmental compensation- Automatic
  • Agency Listings- CAN/ULC-S529, CAN/ULC-S530, UL 268-7, UL 268A, UL 521
  • Operating voltage- 15.20 to 19.95 VDC
  • Normal operating current- 32 µA
  • Alarm current- 45 µA
  • Vibration level- 10 to 35 Hz, with an amplitude of 0.01 in.
  • Smoke Sensitivity Range- UL/ULC: 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) obscuration
  • Rate-of-rise rating- 15°F/min (8°C/min)
  • Fixed temperature rating- 135°F (57.2°C). Actual alarm point 129 to 141°F (53.9 to 60.6°C).
  • Air velocity- 0 to 4,000 ft./min (0 to 20.32 m/s)
  • Wall mounting- 12 in. (305 mm) max. from ceiling
  • Spacing, heat detectors- Max. 50 ft. (15.2 m) centers
  • Compatible bases- See Ordering Information
  • Compatible detector testers- Testifire 1000, Testifire 2000
  • Operating environment- 32 to 100°F (0 to 38°C), 0 to 93% RH, noncondensing
  • Construction- High Impact Engineering Polymer, White
  • Storage temperature- -4 to 140°F (-20 to 60°C)
  • Environmental compensation- Automatic
  • Agency Listings- CAN/ULC-S529, CAN/ULC-S530, UL 268-7, UL 268A,
    UL 521