Functional principle: combined smoke/heat detector (Tyndall effect, NTC sensor
Monitoring area, mounting height: dependent on active detection principle (smoke or heat detector) 1)
permissible air speed: max. 20 m/s
Responsiveness smoke detector
Responsiveness acc. to EN 54-7: 100% Sensitivity
Responsiveness acc. to EN 54-7, not VdS approved: 80% Sensitivity
Responsiveness not acc. to EN 54-7: 120% Sensitivity
Responsiveness heat detector acc. to EN 54-5: Class A1 (Factory setting and after reset)
Class A2, Class B
Index S and R
Multiple sensor detector acc. to EN 54-29: Combination smoke and heat detector
Signal transmission: serial biphase data transmission, 2-wire-system
Operating voltage range (incl. modulation swing)
for SecuriLine operation: 11 to 31 V DC
for SecuriLine eXtended operation: 7 to 31 V DC
Current consumption: max. 0.15 mA
alarm-LED active additionally: max. 2.5 mA
alarm output active additionally: max. 7.5 mA
Alarm output 2) 3)
output voltages: +6.8V DC (-10%, +15%), +5.0V DC (+1V, -0.3V)
output current, current limited (short circuit proof)
nominal 0.1 mA: max. 0.7 mA
nominal 1.0 mA: max. 2.1 mA
nominal 5.0 mA: max. 7.5 mA
Protection system in connection with base USB 502: IP 44 4)
Approval by VdS G210152: according to CEA 4021 part B and C EN 54 part 7, 5, 17 and 29 5)
Declaration of performance: CPR-30-13-302-de-en
Ambient temperature range (continuous): -25 … +60 °C
Ambient conditions humidity: 10 … 95 % rel hum
(continuously, without condensation) at ≤ 34 °C
Ambient conditions humidity: max. 35 g/m³
(continuously, without condensation) at > 34 °C: min. 10% rel hum
Dimensions without base Ø x : see dimensional drawing
Housing colour: white similar to RAL 9003
Housing material: ABS/PC
Weight: 125 g