The Signature Series AB4G sounder bases add audible output functions to any Signature Series detector. Bases can operate as independent local alarms, or as part of a zone or system alarm with synchronized audible output.
Three models provide a full range of features that meet application needs and mandated code-compliant requirements:
SIGA-AB4G bases provide sounder capability to Signature Series single-function smoke detectors. They are not intended for use with combination smoke/CO devices in Fire-plus-CO mode.
All bases are compatible with first and second generation Signature Series intelligent detectors when properly configured. SIGA-AB4G sounder bases match the finish of Signature Series devices, and the sound output slots complement the air entry openings of the detector. The result is a compact unit with an at- tractive appearance.
Operating Current: The operating current for the Edwards EST SIGA-AB4G sounder base, depending on the voltage (16-33 Vdc or 16-33 Vfwr), ranges from 17 mA to 66 mA (RMS)
Supervisory Current: DC = 1.46 mA, FWR = 2.15 mA
Default Output Volume: High dBA
Default Tone: Temporal
Resonant frequency: 3.2 kHz
Temporal pattern: 0.5 s on, 0.5 s off,0.5 s on, 0.5 s off,
0.5 s on, 1.5 s off, repeat cycle
Compatible detectors: All Signature Series detectors
Compatible electrical boxes: AB4G-SB surface box for audible base; 4 in. square by 2-1/8 in. (54 mm) deep box; 3-1/2 in. octagonal by 2-1/8 in. (54 mm) deep box; Standard European 100 mm² box
Wire size: 12 to 18 AWG (0.75 to 2.50 mm²)
Base diameter: 6.8 in. (173 mm)
Base height from box: 0.8 in. (21 mm)
Maximum distance from ceiling Wall mount: 12 in. (305 mm)
Environment type: Indoor only
Operating environment Temperature Relative humidity: 32 to 120°F (0 to 49°C) 0 to 93% noncondensing