TX7004 Intelligent Addressable Fire Alarm Control Panel

The TX7004 comprise of a range of analogue addressable, microprocessor-based fire alarm control equipment to offer flexibility in both design and operation. The System is modular concept for easy tailoring of system design, to meet the full requirements of the project. The TX7004 Intelligent Fire Alarm Control Panel is designed and manufactured to meet the requirement of BS EN54 Part 2&4. The TX7004 is designed to provide early warning fire detection, to quickly identify the location of fire and provide user definable text informing the occupants of the building of potential smoke spread. Simultaneously, the TX7004 will alert and evacuate the occupants, and control all necessary auxiliary command functions such as elevator control, air handling shut down, gas shut off & damper control, as per the cause and effects requirements configured though Command Builder Set-up.

Features and Benefits
• Certified EN54-2:1997 +A1:2006, EN54-4:1997 +
A1:2002 + A2:2006
• LPCB Approved
• Using advance microprocessor technology
with Large memory capacity
• Enhance user interface combining LCD Touch
screen and keypad access
• Support real time visual algorithm
• Enhance false alarm prevention
• Keypad and PC programming
• Built-in Multiple interface protocol such as
USB/Ethernet/CanBus/ Serial/RS485 (Available
only in TX7004/4 Panel)
• Support Loop Powered devices for extra
saving on cable cost
• Built-In Printer and 160 LED Zones Indicators

  • Type: Intelligent Addressable Fire Alarm Control Panel
  • Housing:
    • Material: Durable steel enclosure
    • Color: Typically neutral (e.g., gray or beige)
    • Dimensions: Approximately 17.5 in. H x 15 in. W x 5 in. D (445 mm x 381 mm x 127 mm)
    • Weight: Approximately 22 lbs (10 kg) with batteries
    • Mounting: Wall-mount, surface or semi-flush
  • Power Supply:
    • Input Voltage: 240 VAC +10%/-15%, 50/60 Hz (optional 120 VAC, 60 Hz version available)
    • Input Current: 1 A maximum
    • PSU Output: 24.5–28.5 VDC to control panel
    • Battery Backup: 2 x 12V, 28 Ah sealed lead-acid batteries (max charge capacity)
    • Charging: 1.2 A max charge current, temperature-compensated
  • Loop Specifications:
    • Loops: 2 or 4 loops standard, expandable to 6 loops (standalone)
    • Device Capacity: Up to 254 addressable devices per loop (1,524 total ideal)
    • Protocol: T&A proprietary addressable protocol
    • Wiring: Twisted pair, up to 3280 ft (1000 m) with 18 AWG
    • Style: Class B (Style 4) or Class A (Style 6) with isolators
  • System Capacity:
    • Zones: Up to 3,000 programmable zones
    • Sounder Groups: 1–1,000 programmable
    • Module Groups: 1,001–2,000 programmable
    • Event Memory: 1,000 fire events, 10,000 general events (non-volatile)
    • Indicators: Built-in 160 LED zone indicators
  • User Interface:
    • Display: Wide LCD touchscreen (color)
    • Controls: Keypad with large buttons for fire brigade access
    • Features: Real-time visual algorithms, enhanced false alarm prevention
    • Programming: Keypad or PC via software
  • Connectivity:
    • Interfaces: USB, Ethernet, CAN Bus, RS232, RS485 (available in 4-loop version)
    • Networking: CAN Bus loop, up to 512 panels
    • Printer: Built-in thermal printer for event logging
  • Outputs and Inputs:
    • Sounder Outputs: Programmable, loop-powered sounders supported
    • Auxiliary Outputs: Fire alarm, fault, and programmable relays
    • Inputs: Configurable for monitoring external devices
  • Environmental Specifications:
    • Operating Temperature: 32°F to 120°F (0°C to 49°C)
    • Humidity: 10% to 93% non-condensing
    • Location: Indoor use only
    • EN 54-2: 1997 + A1: 2006
    • EN 54-4: 1997 + A1: 2002 + A2: 2006
    • LPCB Approved
    • NFPA 72: Compatible with requirements when configured appropriately