TX7200 Addressable Input Module

The TX7200 Addressable Input Module is used to acknowledge normally open monitor signal from interface equipment then sending communication signal to the control panel, ideally for monitoring sprinkler system, pressure switch, position switch, signal valves and other third party equipment such as conventional panel. The unit manufactured base on the requirement of EN 54 part 18, European Standard. The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs and its plug-in type assembles make installation and maintenance more convenient to the installer. The unit incorporates an intelligent processor that provides automatic monitoring for both open and short circuit of the input signal line. The TX7200 Input Module is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel, produced by single manufacture T&A, to avoid addressable communication compatibility problem.
  • EN54-18 Compliance
  • LPCB Pending
  • Built-in MCU processor and digital addressing
  • Input cable monitored
  • LED status indicator
  • Loop powered device
  • Aesthetically pleasing design
  • Surface mounting with fix base for simple installation
  • Normal open configuration
  • File or Supervisory signal configuration
  • Listed: LPCB Pending
  • Compliance: EN54-18:2005/AC2007
  • Input Voltage: 24VDC [16V to 28V]
  • Current Consumption Standby: 0.6mA, Alarm: 1.0Ma
  • Protocol/ Addressing: T&A, Value range from 1 to 254
  • Input Relay: Normally Open dry contact
  • Input Resistance: 5.1Kohms/ ¼ W
  • Indicator Status Normal: Single blink/Active: Steady/Fault: Double Blink
  • Material/Colour: ABS/White Glossy finishing
  • Dimension/LWH: 108 mm x 86 mm x38 mm
  • Weight: 155g (with Base), 85g (without Base)
  • Operating Temperature: -10°C to +50°C
  • Ingress Protection Rating: IP30
  • Humidity: 0 to 95% Relative Humidity, Non condensing