3-ZA20A | 3-ZA40A | 3-ZA95 | |
Agency Listing | UL, ULC, CE, EN54 EN 54-2: 1997 + A1: 2006, EN 54-4: 1997 + A1: 2002 + A2: 2006, and EN 54-16: 2008 |
UL, ULC | |
Environmental | 0°C – 49°C (32°F – 120°F) 93% RH, Non-condensing | ||
Frequency Response | 400Hz to 4KHz @ +/- 3dB | ||
Output Voltage | 25 VRMS or 70 VRMS | ||
THD (distortion) | < 7% | ||
Wire Size | 18 to 12 AWG (1.0 to 2.5 mm²) | ||
Internal Tone Generator |
1KHz Temporal (3-3-3) Tone (evacuation); 20 PPM (alert) | ||
SIGA-CC1/2 Support | 10 Units, Maximum | ||
Standby Current | 62mA for 20 and 40 watt amps; 85mA for the 3-ZA95 watt amp |
||
Alarm Current | 1120mA | 2480mA | 5540mA |
Pwr. Ltd. Audio Output Wiring Configuration EOL Resistor |
Class A or B 15K Ohms in Class B |
Class A or B 15K Ohms in Class B |
Class A or B 15K Ohms in Class B |
Pwr. Ltd. 24 Vdc NAC Wiring Configuration Line Resistance, Max.* EOL Resistor Line Capacitance, Max |
Class A or B 50 Ohms, Max. N/A 0.33µF |
Class A or B 50 Ohms, Max. N/A 0.33µF |
N/A |
Space Requirements | 1 LRM Space | 2 LRM Spaces | |
Note: *For EN 54-2: 1997 + A1: 2006, EN 54-4: 1997 + A1: 2002 + A2: 2006, and EN 54-16: 2008 compliant product add suffix -E to model eg. 3-ZA20A-E. | |||
Maximum Speaker Circuit Distance at 0.5 dB loss* | |||
70 VRMS Output | 3-ZA20A | 3-ZA40A | 3-ZA95 |
#12 AWG (3.2 Ohm/1000 ft pair) |
4,536 ft (1,382 m) | 2,268 ft (691 m) | 955 ft (290 m) |
#14 AWG (5.2 Ohm/1000 ft pair) |
2,792 ft (850 m) | 1,396 ft (425 m) | 588 ft (179 m) |
#16 AWG (8.0 Ohm/1000 ft pair) |
1,815 ft (553 m) | 907 ft (276 m) | 382 ft (116 m) |
#18 AWG (13 Ohm/1000 ft pair) |
1,117 ft (340 m) | 558 ft (170 m) | 235 ft (71 m) |
25 VRMS Output | 3-ZA20A | 3-ZA40A | 3-ZA95 |
#12 AWG (3.2 Ohm/1000 ft pair) |
579 ft (176 m) | 289 ft (88 m) | 122 ft (37 m) |
#14 AWG (5.2 Ohm/1000 ft pair) |
356 ft (108 m) | 178 ft (54 m) | 75 ft (22 m) |
#16 AWG (8.0 Ohm/1000 ft pair) |
231 ft (70 m) | 116 ft (35 m) | 49 ft (14 m) |
#18 AWG (13 Ohm/1000 ft pair) |
142 ft (43 m) | 71 ft (21 m) | Not supported by 18 AWG |